514067-UAD-B-0909APPLICATION GUIDEOVERVIEWThe Simplicity®LINC Gateway operates as a Modbus® Client providing an interface between a BACnet® MS/TP cont
514067-UAD-B-090910 Johnson Controls Unitary ProductsTABLE 3: POINTS LIST IN OBJECT ORDERRead/WriteBACnet Object TypeBACnet Object Inst Descriptor Def
514067-UAD-B-0909Johnson Controls Unitary Products 11TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)Read/WriteBACnet Object TypeBACnet Object Inst De
514067-UAD-B-090912 Johnson Controls Unitary ProductsTABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)Read/WriteBACnet Object TypeBACnet Object Inst De
514067-UAD-B-0909Johnson Controls Unitary Products 13TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)Read/WriteBACnet Object TypeBACnet Object Inst De
514067-UAD-B-090914 Johnson Controls Unitary ProductsTABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)Read/WriteBACnet Object TypeBACnet Object Inst De
514067-UAD-B-0909Johnson Controls Unitary Products 15TABLE 3: POINTS LIST IN OBJECT ORDER (CONTINUED)Read/WriteBACnet Object TypeBACnet Object Inst De
514067-UAD-B-090916 Johnson Controls Unitary ProductsTROUBLESHOOTINGThe Simplicity®LINC Gateway consists of two printed circuit boards.TABLE 4: SIMPLI
514067-UAD-B-0909Johnson Controls Unitary Products 17 FIGURE 3: SIMPLICITY®LINC GATEWAY LED LOCATIONPWR (RS485)PWR (BACnet)GP105 (BACnet)LB(BACnet)RX
Subject to change without notice. Printed in U.S.A. 514067-UAD-B-0909Copyright © 2009 by Johnson Controls, Inc. All rights reserved. Supersedes: 51406
514067-UAD-B-09092 Johnson Controls Unitary ProductsCONNECTIONThe Simplicity®LINC has 2 ports, one for connection to the BAS network (BACnet) and one
514067-UAD-B-0909Johnson Controls Unitary Products 3FLASH MEMORY MANAGEMENTThe Flash Memory chip used in the Simplicity® controllers has a 1,000,000 w
514067-UAD-B-09094 Johnson Controls Unitary ProductsTABLE 2: POINTS LIST IN DESCRIPTION ORDERRead/WriteBACnet Object TypeBACnet Object Inst Descriptor
514067-UAD-B-0909Johnson Controls Unitary Products 5TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)Read/WriteBACnet Object TypeBACnet Object Ins
514067-UAD-B-09096 Johnson Controls Unitary ProductsTABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)Read/WriteBACnet Object TypeBACnet Object Ins
514067-UAD-B-0909Johnson Controls Unitary Products 7TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)Read/WriteBACnet Object TypeBACnet Object Ins
514067-UAD-B-09098 Johnson Controls Unitary ProductsTABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)Read/WriteBACnet Object TypeBACnet Object Ins
514067-UAD-B-0909Johnson Controls Unitary Products 9TABLE 2: POINTS LIST IN DESCRIPTION ORDER (CONTINUED)Read/WriteBACnet Object TypeBACnet Object Ins